Article | REF: TBA3046 V1

ERP fire safety - Technical instruction no. 263 on the construction and smoke extraction of interior open spaces

Authors:

Publication date: December 10, 2013, Review date: March 1, 2021

You do not have access to this resource.
Click here to request your free trial access!

Already subscribed? Log in!


Français

2. Small atriums

2.1 Definition

Small atria are located in buildings where the highest floor is no higher than 8 m above the atrium level (R + 2 or R + 1 with basement). Their basic cross-section is at least 5 × 5 m.

SCROLL TO TOP

2.2 Smoke extraction in small atriums

Smoke extraction is carried out :

  • or naturally through openings installed in the upper part of the atrium and representing a free area equal to 1/100 of the basic cross-section with a minimum of 2 m ...

You do not have access to this resource.

Exclusive to subscribers. 97% yet to be discovered!

You do not have access to this resource.
Click here to request your free trial access!

Already subscribed? Log in!


The Ultimate Scientific and Technical Reference

A Comprehensive Knowledge Base, with over 1,200 authors and 100 scientific advisors
+ More than 10,000 articles and 1,000 how-to sheets, over 800 new or updated articles every year
From design to prototyping, right through to industrialization, the reference for securing the development of your industrial projects

This article is included in

Preparing for construction

This offer includes:

Knowledge Base

Updated and enriched with articles validated by our scientific committees

Services

A set of exclusive tools to complement the resources

Practical Path

Operational and didactic, to guarantee the acquisition of transversal skills

Doc & Quiz

Interactive articles with quizzes, for constructive reading

Subscribe now!

Ongoing reading
Small atriums