4. System-specific provisions

4.1 Solution A

Air inlets for intercommunication devices have their upper edge no more than 1 m above the floor.

Smoke extraction outlets on intercommunication devices have their bottom part at least 1.80 m above the floor and are located entirely in the upper third of the device.

The air supply and smoke extraction vents of intercommunication devices are fitted with flame-retardant shutters rated at 1 h or E 60, closed in the standby position.

The air supply and smoke extraction flow rates in intercommunication devices are at least 0.20 m 3 /s/m 2 . As intercommunication devices must always be overpressurized in relation...

You do not have access to this resource.

Exclusive to subscribers. 97% yet to be discovered!

You do not have access to this resource.
Click here to request your free trial access!

Already subscribed? Log in!


The Ultimate Scientific and Technical Reference

A Comprehensive Knowledge Base, with over 1,200 authors and 100 scientific advisors
+ More than 10,000 articles and 1,000 how-to sheets, over 800 new or updated articles every year
From design to prototyping, right through to industrialization, the reference for securing the development of your industrial projects

This article is included in

Preparing for construction

This offer includes:

Knowledge Base

Updated and enriched with articles validated by our scientific committees

Services

A set of exclusive tools to complement the resources

Practical Path

Operational and didactic, to guarantee the acquisition of transversal skills

Doc & Quiz

Interactive articles with quizzes, for constructive reading

Subscribe now!

Ongoing reading
System-specific provisions